Cat XLM Switchgear

Cat XLM Switchgear

Cat XLM Switchgear

DESCRIPTION

The Emergency Transfer and Load management (XLM) product supports transfer between the utility source and generator bus and allows for sustained parallel operation with the utility for load management applications.The Emergency Transfer and Load management (XLM) product supports transfer between the utility source and generator bus and allows for sustained parallel operation with the utility for load management applications.Electric Power

XLM Switchgear

  • High Speed Supervisory Network
  • Automatic Start/Stop
  • Automatic “Dead Bus” Coordination
  • Automatic Power Factor Control when in Parallel with Utility Power
  • Programmable Load Shed / Load Add Functions
  • Networked Engine Communications
  • Generator & Utility Protection
  • Engine Tuning
  • Mode Selection
  • Selectable Auto/ Manual Control
  • Password Protection for Protective Settings and Setup
  • Load/No Load Test
  • Touch Screen (HMI) Display
  • NFPA 99/110 Compliant Alarm
  • Annunciation with Audible Horn
  • Engine Control mimic Screen with gauges for RPM, DC Battery Voltage, Oil Pressure, Engine Coolant temperature, Engine Hours, Number of starts

  • Standard Equipment
  • Optional Equipment
  • Specs
  • Docs

Standard Equipment

Optional Equipment

Specs

Overview

Long Name:
Cat XLM Switchgear
Name:
Cat XLM Switchgear
Brand:
Caterpillar
Status:
Current

Technical Summary

Configuration
Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
Modes of Operation
Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application
LV and MV ( 208V - 38 kV

Generator Protective Devices

ANSI Protective Devices
15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices
15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86

Environmental Parameters

Certifications
IBS, CBC, UBC & OSHPD Certified
Control Panel Enclosure
NEMA 1 or NEMA 3R, Freestanding Construction
Operating Temperature
0 degrees to 50 degrees C
Storage Temperature
-20 degrees C to +60 degrees C
Low Voltage Standards
NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards
NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110

SEE HOW Cat XLM Switchgear COMPARES AGAINST FREQUENTLY COMPARED PRODUCTS.

Switchgear and Paralleling Controls
Cat XLM Switchgear
Cat XLM Switchgear
Brand
Caterpillar
Status
Current
Configuration
Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
Modes of Operation
Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application
LV and MV ( 208V - 38 kV
Operating Temperature
0 degrees to 50 degrees C
Switchgear and Paralleling Controls
Cat Switchgear
Cat Switchgear
Brand
Caterpillar
Status
Current
Configuration
IP4X
Modes of Operation
Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc.
Application
LV 380…480 VAC, 50 Hz, 3-Phase.
Operating Temperature
35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F)
Switchgear and Paralleling Controls
EMCP 4.4 Master Control Panel
Master Control Panel
Brand
Caterpillar
Status
Current
Configuration
Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source.
Modes of Operation
Emergency standby, island, utility paralleling
Application
LV and MV (208V - 38 kV)
Operating Temperature
0°C to 50°C