Power System

3512B Diesel Generator Set

1600 - 1875 kVA Diesel Generator Set

Producing reliable power from 1600 to 1875 kVA at 50 Hz, our 3512B diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We’ve designed each to ISO 8528-5 transient response requirements and to accept 100% rated load in one step. Cat® generator sets offer both low fuel consumption and low emission systems.
FAQ
Q. Does this generator comply with ISO 8528 guidelines?
A. Yes, the 3512B, like all Cat generators, is tested in accordance with the load steps outlined in with ISO 8528, Part 5.
Q. Are Cat generators easy to install?
A. Cat generators can be configured with a number of options for ease of installation.
Q .Does Cat’ have much experience with electric power generation?
A. Cat has over 80 years experience with on-site and portable power and has shipped millions of generators to customers around the world.
Q. Does Cat offer generators that support my Sustainability goals?
A. Cat offers generators that can run on a number of renewable fuels including HVO, biodiesel, landfill gas, sewage gas and more.
Q. Will this generator be able to provide emergency power on hot summer days?
A. Most Cat 3500 Series generators can operate in ambient temperatures up to 50°C (122°F), reliably providing power when it is needed.

1600 – 1875 kVA at 50 Hz Diesel Genset
The 3512B generator set has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters to continuously powering remote installations. The packages can be optimized for performance that matters to you with either low emissions or low fuel consumption versions available. Backed by the worldwide network of Cat dealers ready to support your operation with technical support, service, parts, and warranty, Cat generator sets will provide the reliability and durability you expect.
Q. Does this generator comply with ISO 8528 guidelines?
A. Yes, the 3512B, like all of our generators, is tested in accordnace the load steps outlined in with ISO 8528, Part 5.

Equipment Highlights

Cat Generator Set Package
  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
EMCP 4 Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
Cooling System
        
  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  •     
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
  • EU Declaration of Conformity
  • EU Declaration of Incorporation
  • Eurasian Conformity (EAC)
  • Telecommunication Lab of China
One Safe Source
  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Specs + Downloads

Specs
  • Engine Model: 3512B TA, V-12, 4-Stroke Water-Cooled Diesel
  • Bore: 6.69 in
  • Stroke: 7.48 in
  • Stroke - HD: 8.46 in
  • Displacement: 3161.03 in³
  • Displacement - HD: 3576 in³
  • Compression Ratio: 15.5:1 HD
  • Aspiration: TA
  • Fuel System: Electronic Unit Injection
  • Governor Type: ADEM™ A3
  • Length - Minimum: 212.8 in
  • Length - Maximum: 217.1 in
  • Width - Minimum: 90 in
  • Width - Maximum: 90 in
  • Height - Minimum: 94.9 in
  • Height - Maximum: 94.9 in
  • Dry Weight - Genset (minimum): 25620 lb
  • Dry Weight - Genset (maximum): 26530 lb
  • Standby Rating: 1875/1750 kVA
  • Prime Power Rating: 1700/1600 kVA
  • Emissions/Fuel Strategy: Low Fuel , Low Emissions
  • Voltage: 400 to 415 Volts
  • Frequency: 50 Hz
  • Speed: 1500 rpm
  • Duty Cycle: Standby, Mission Critical, Prime, Continuous
  • Minimum Rating: 1600 kVA
  • Maximum Rating: 1875 kVA

Photo Gallery

Let us help you find what you are looking for.