3412C | 750kVA
3412C | 750kVA 50Hz Generator Set
3412C (50 HZ) 680-900 kVA Diesel Generator models provide unmatched flexibility, expandability, reliability, & cost-effectiveness for prime & standby needs.
DESCRIPTION
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR500 Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
EMCP 4 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 50°C (122°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
- EU Declaration of Conformity
- EU Declaration of Incorporation
- Eurasian Conformity (EAC)
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
- Standard Equipment
- Optional Equipment
- Specs
- Docs
Standard Equipment
- Air Inlet System
- Air cleaner, single element canister type with service indicator
- Control Panel
- GCCP Control panel
- Over/under voltage (27 / 59)
- Environmental sealed front face
- Generator phase sequence
- Communications
- Digital I/O module
- Features include:
- 2 Programmable relay outputs (Form C)
- Compatible with the following optional modules:
- Customer data link (Modbus RTU)
- 4 programmable relay outputs (Form A)
- Amps (per phase & average)
- kVA (per phase, average & percent)
- Text alarm/event descriptions
- Low coolant level
- Generator temperature monitoring module
- Run/auto/ stop/control
- Overspeed
- Serial annunciator module data link
- Emergency stop pushbutton
- Frequency (Hz)
- RPM
- 6 programmable digital inputs
- Oil pressure (psi, kPa or bar)
- Engine cycle crank
- Operating hours
- Local annunciator
- coolant temperature
- kW-hr (total)
- Programmable protective relaying functions:
- kW (per phase, average & percent)
- Low oil pressure
- Reverse power (kW) (32)
- Remote Serial annunciator
- DC volts
- Power factor (per phase & average)
- Remote CAN annunciator
- 24 Volt DC operation
- Accessory module data link
- Failure to start (overcrank)
- Over/under frequency (81 o/u)
- kVAr (per phase, average & percent)
- Warning/shutdown with common LED indication of shutdowns for:
- Low coolant temperature
- 2 Programmable digital outputs
- Reverse reactive power (kVAr) (32RV)
- Emergency stop
- Digital indication for:
- High coolant temperature
- Speed adjust
- Voltage adjust
- Volts (L-L & L-N)
- Overcurrent (50 / 51)
- Cooling System
- Fan and belt guards
- Coolant drain line with valve, piped to edge of base
- Caterpillar extended life coolant
- Coolant level shutdown
- Radiator with guard (Sized for 50 degrees C)
- Exhaust System
- Stainless steel exhaust flex with ANSI style outlet flange, gasket, bolts and mating weld flange, shipped loose
- Fuel System
- Flexible fuel lines terminated on base
- Fuel priming pump
- Primary and Secondary fuel filters
- Water seperator
- Generator and Attachments
- 3-phase sensing
- SR4B self excited
- Class H insulation
- 2:1 Volts/Hz
- Reactive droop
- VR6 voltage regulator
- Busbar termination
- Class F temperature rise
- 12 Leads
- Governing System
- Cat electronic governor
- Lube System
- Oil drain line with valve, piped to edge of base
- Lubricating oil
- Oil filter
- Fumes disposal, piped to front of radiator
- Mounting System
- Base, formed steel with linear vibration isolators between base and engine-generator
- Starting / Charging System
- Battery with rack, cables
- 45 amp Charging alternator
- 24 volt starting motor
- Fuel shutoff solenoid
Optional Equipment
- Air Inlet System
- Open element air cleaners
- Heavy duty air cleaners
- Dual element air cleaners
- Circuit breakers
- 1600 Amp, 3 pole, Non-UL, 100% rated, 24 volt DC shunt trip
- 1250, 1600 Amp, 3 pole, IEC 100% rated, 24 volt DC shunt trip
- Control Panel
- First local annunicators
- Local discrete I/O package
- Generator temperature monitoring package
- Ground fault relay
- Remote custom annunicator
- GCCP Control panel
- Generator running VFC
- GCCP Control panel
- Vandal proof panel door
- Common alarm/shutdown relay
- Cooling System
- Jacket water heaters
- Radiator duct flange
- European Certifications
- Eurasian Conformity (EAC) mark
- Exhaust System
- Elbow kit
- Manifold and turbocharger guards
- Through wall installation kit
- Mufflers
- Generator and Attachments
- Digital voltage regulator
- Oversize and premium generators
- Space heater
- Permanent magnet excitation (PMG)
- Lube System
- Manual sump pump
- Mounting System
- Fuel tank base (1200 ltr)
- Special Tests / Reports
- PGS Test report @ 1.0 power factor
- PGS Test report @ 0.8 power factor
- Starting / Charging
- Heavy duty starting system
- Battery chargers
- Battery disconnect switch
- Oversize batteries
- Governing System
- Electronic load share
Specs
Overview
Long Name:
3412C | 750kVA 50Hz Generator Set
Name:
3412C | 750kVA
Brand:
Cat
Status:
Current
Generator Set Specifications
Maximum Rating
680 kVA
Minimum Rating
680 kVA
Emissions/Fuel Strategy
Low Fuel Consumption
Voltage
380 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Prime
Engine Specifications
Engine Model
3412C TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
5.4 in / 137.2 mm
Stroke
6 in / 152.4 mm
Displacement
1648.86 in³ / 27.02 l
Compression Ratio
13:01
Aspiration
Turbocharged, Air to Air Aftercooled
Fuel System
Pump and Lines
Governor Type
ADEM™ A5
Generator Set Dimensions
Length - Maximum
162.4 in / 4125 mm
Width - Minimum
75 in / 1906 mm
Width - Maximum
78.3 in / 1989 mm
Height - Maximum
75 in / 1906 mm
Dry Weight - Genset (minimum)
12039 lb / 5461 kg
Dry Weight - Genset (maximum)
13030 lb / 5910 kg
SEE HOW 3412C | 750kVA COMPARES AGAINST FREQUENTLY COMPARED PRODUCTS.
Diesel Generator Sets
3412C | 750kVA
- Brand
- Cat
- Status
- Current
- Maximum Rating
- 680 kVA
- Minimum Rating
- 680 kVA
- Emissions/Fuel Strategy
- Low Fuel Consumption
- Voltage
- 380 to 415 Volts
- Frequency
- 50 Hz
- Speed
- 1500 rpm
- Duty Cycle
- Standby, Prime
- Engine Model
- 3412C TA, V-12, 4-Stroke Water-Cooled Diesel
- Bore
- 5.4 in / 137.2 mm
- Stroke
- 6 in / 152.4 mm
- Displacement
- 1648.86 in³ / 27.02 l
- Compression Ratio
- 13:01
- Aspiration
- Turbocharged, Air to Air Aftercooled
- Fuel System
- Pump and Lines
- Governor Type
- ADEM™ A5
- Length - Maximum
- 162.4 in / 4125 mm
- Width - Maximum
- 78.3 in / 1989 mm
- Height - Maximum
- 75 in / 1906 mm
- Dry Weight - Genset (minimum)
- 12039 lb / 5461 kg
- Dry Weight - Genset (maximum)
- 13030 lb / 5910 kg
Selected Model
Diesel Generator Sets
3412C (60 Hz)
- Brand
- Cat
- Status
- Current
- Maximum Rating
- 800 ekW
- Minimum Rating
- 635 ekW
- Emissions/Fuel Strategy
- Low Fuel Consumption
- Voltage
- 220 to 480 Volts
- Frequency
- 60 Hz
- Speed
- 1800 rpm
- Duty Cycle
- Standby, Prime
- Engine Model
- 3412C TA, V-12, 4-Stroke Water-Cooled Diesel
- Bore
- 5.4 in / 137.2 mm
- Stroke
- 6 in / 152.4 mm
- Displacement
- 1648.86 in³ / 27.02 l
- Compression Ratio
- 13:00:01
- Aspiration
- TA
- Fuel System
- Pump and Lines
- Governor Type
- ADEM™ A5
- Length - Maximum
- 162.4 in / 4125 mm
- Width - Maximum
- 78.3 in / 1989 mm
- Height - Maximum
- 75 in / 1906 mm
- Dry Weight - Genset (minimum)
- 5761 lb / 12700 kg
- Dry Weight - Genset (maximum)
- 13275 lb / 6021 kg
Diesel Generator Sets
3412C (50 Hz)
- Brand
- Cat
- Status
- Current
- Maximum Rating
- 900 kVA
- Minimum Rating
- 680 kVA
- Emissions/Fuel Strategy
- Low Fuel Consumption
- Voltage
- 380 to 415 Volts
- Frequency
- 50 Hz
- Speed
- 1500 rpm
- Duty Cycle
- Standby, Prime
- Engine Model
- 3412C TA, V-12, 4-Stroke Water-Cooled Diesel
- Bore
- 5.4 in / 137.2 mm
- Stroke
- 6 in / 152.4 mm
- Displacement
- 1648.86 in³ / 27.02 l
- Compression Ratio
- 13:01
- Aspiration
- TA
- Fuel System
- Pump and Lines
- Governor Type
- ADEM™ A5
- Length - Maximum
- 162.4 in / 4125 mm
- Width - Maximum
- 78.3 in / 1989 mm
- Height - Maximum
- 75 in / 1906 mm
- Dry Weight - Genset (minimum)
- 12039 lb / 5461 kg
- Dry Weight - Genset (maximum)
- 13030 lb / 5910 kg