3412C | 900 kVA

3412C | 900 kVA 50Hz Generator Set

3412C (50 HZ) 680-900 kVA Diesel Generator models provide unmatched flexibility, expandability, reliability, & cost-effectiveness for prime & standby needs.

3412C Front Left

DESCRIPTION

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR500 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP 4 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • EU Declaration of Conformity
  • EU Declaration of Incorporation
  • Eurasian Conformity (EAC)

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

  • Standard Equipment
  • Optional Equipment
  • Specs
  • Docs

Standard Equipment

  • Air Inlet System
    • Air cleaner, single element canister type with service indicator
  • Control Panel
    • GCCP Control panel
    • Emergency stop pushbutton
    • Overspeed
    • Text alarm/event descriptions
    • Low coolant temperature
    • Frequency (Hz)
    • Overcurrent (50 / 51)
    • 4 programmable relay outputs (Form A)
    • Volts (L-L & L-N)
    • Programmable protective relaying functions:
    • Warning/shutdownn with common LED indication of shutdowns for:
    • 24 Volt DC operation
    • Over/under voltage (27 / 59)
    • Engine cycle crank
    • Over/under frequency (81 o/u)
    • Remote CAN annunciator
    • Remote Serial annunciator
    • kW (per phase, average & percent)
    • Digital I/O module
    • Failure to start (overcrank)
    • Low oil pressure
    • Low coolant level
    • Run/auto/ stop/control
    • 6 programmable digital inputs
    • Accessory module data link
    • Features include:
    • Compatible with the following optional modules:
    • Serial annunciator module data link
    • kVA (per phase, average & percent)
    • Voltage adjust
    • RPM
    • Generator temperature monitoring module
    • kVAr (per phase, average & percent)
    • 2 Programmable relay outputs (Form C)
    • DC volts
    • Communications
    • Local annunciator
    • Power factor (per phase & average)
    • Speed adjust
    • Emergency stop
    • Reverse power (kW) (32)
    • coolant temperature
    • Digital indication for:
    • Reverse reactive power (kVAr) (32RV)
    • Customer data link (Modbus RTU)
    • kW-hr (total)
    • Amps (per phase & average)
    • High coolant temperature
    • Generator phase sequence
    • Oil pressure (psi, kPa or bar)
    • Operating hours
    • 2 Programmable digital outputs
    • Environmental sealed front face
  • Cooling System
    • Fan and belt guards
    • Radiator with guard (Sized for 50 degrees C)
    • Coolant drain line with valve, piped to edge of base
    • Coolant level shutdown
    • Caterpillar extended life coolant
  • Exhaust System
    • Stainless steel exhaust flex with ANSI style outlet flange, gasket, bolts and mating weld flange, shipped loose
  • Fuel System
    • Primary and Secondary fuel filters
    • Water seperator
    • Flexible fuel lines terminated on base
    • Fuel priming pump
  • Generator and Attachments
    • 3-phase sensing
    • Busbar termination
    • SR4B self excited
    • 2:1 Volts/Hz
    • Class F temperature rise
    • 12 Leads
    • Class H insulation
    • Reactive droop
    • VR6 voltage regulator
  • Governing System
    • Cat electronic governor
  • Lube System
    • Oil drain line with valve, piped to edge of base
    • Oil filter
    • Fumes disposal, piped to front of radiator
    • Lubricating oil
  • Mounting System
    • Base, formed steel with linear vibration isolators between base and engine-generator
  • Starting / Charging System
    • Fuel shutoff solenoid
    • 45 amp Charging alternator
    • Battery with rack, cables
    • 24 volt starting motor

Optional Equipment

  • Air Inlet System
    • Dual element air cleaners
    • Heavy duty air cleaners
    • Open element air cleaners
  • Circuit breakers
    • 1250, 1600 Amp, 3 pole, IEC 100% rated, 24 volt DC shunt trip
    • 1600 Amp, 3 pole, Non-UL, 100% rated, 24 volt DC shunt trip
  • Control Panel
    • Ground fault relay
    • Vandal proof panel door
    • First local annunicators
    • Common alarm/shutdown relay
    • Remote custom annunicator
    • GCCP Control panel
    • Generator running VFC
    • GCCP Control panel
    • Local discrete I/O package
    • Generator temperature monitoring package
  • Cooling System
    • Radiator duct flange
    • Jacket water heaters
  • European Certifications
    • Eurasian Conformity (EAC) mark
  • Exhaust System
    • Manifold and turbocharger guards
    • Through wall installation kit
    • Elbow kit
    • Mufflers
  • Generator and Attachments
    • Permanent magnet excitation (PMG)
    • Space heater
    • Digital voltage regulator
    • Oversize and premium generators
  • Lube System
    • Manual sump pump
  • Mounting System
    • Fuel tank base (1200 ltr)
  • Special Tests / Reports
    • PGS Test report @ 0.8 power factor
    • PGS Test report @ 1.0 power factor
  • Starting / Charging
    • Battery disconnect switch
    • Heavy duty starting system
    • Battery chargers
    • Oversize batteries
  • Governing System
    • Electronic load share

Specs

Overview

Long Name:
3412C | 900 kVA 50Hz Generator Set
Name:
3412C | 900 kVA
Brand:
Cat
Status:
Current

Generator Set Specifications

Maximum Rating
680 kVA
Minimum Rating
680 kVA
Emissions/Fuel Strategy
Low Fuel Consumption
Voltage
380 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Prime

Engine Specifications

Engine Model
3412C TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
5.4 in / 137.2 mm
Stroke
6 in / 152.4 mm
Displacement
1648.86 in³ / 27.02 l
Compression Ratio
13:01
Aspiration
Turbocharged, Air to Air Aftercooled
Fuel System
Pump and Lines
Governor Type
ADEM™ A5

Generator Set Dimensions

Length - Maximum
162.4 in / 4125 mm
Width - Minimum
75 in / 1906 mm
Width - Maximum
78.3 in / 1989 mm
Height - Maximum
75 in / 1906 mm
Dry Weight - Genset (minimum)
12039 lb / 5461 kg
Dry Weight - Genset (maximum)
13030 lb / 5910 kg

SEE HOW 3412C | 900 kVA COMPARES AGAINST FREQUENTLY COMPARED PRODUCTS.

Diesel Generator Sets
3412C | 900 kVA
3412C Front Left
Brand
Cat
Status
Current
Maximum Rating
680 kVA
Minimum Rating
680 kVA
Emissions/Fuel Strategy
Low Fuel Consumption
Voltage
380 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Prime
Engine Model
3412C TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
5.4 in / 137.2 mm
Stroke
6 in / 152.4 mm
Displacement
1648.86 in³ / 27.02 l
Compression Ratio
13:01
Aspiration
Turbocharged, Air to Air Aftercooled
Fuel System
Pump and Lines
Governor Type
ADEM™ A5
Length - Maximum
162.4 in / 4125 mm
Width - Maximum
78.3 in / 1989 mm
Height - Maximum
75 in / 1906 mm
Dry Weight - Genset (minimum)
12039 lb / 5461 kg
Dry Weight - Genset (maximum)
13030 lb / 5910 kg
Diesel Generator Sets
3412C | 800 kVA
3412C Front Left
Brand
Cat
Status
Current
Maximum Rating
680 kVA
Minimum Rating
680 kVA
Emissions/Fuel Strategy
Low Fuel Consumption
Voltage
380 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Prime
Engine Model
3412C TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
5.4 in / 137.2 mm
Stroke
6 in / 152.4 mm
Displacement
1648.86 in³ / 27.02 l
Compression Ratio
13:01
Aspiration
Turbocharged, Air to Air Aftercooled
Fuel System
Pump and Lines
Governor Type
ADEM™ A5
Length - Maximum
162.4 in / 4125 mm
Width - Maximum
78.3 in / 1989 mm
Height - Maximum
75 in / 1906 mm
Dry Weight - Genset (minimum)
12039 lb / 5461 kg
Dry Weight - Genset (maximum)
13030 lb / 5910 kg
Diesel Generator Sets
3512 (50 Hz)
3512 MUI Modular Rear Overhang Generator Set (Rear Right)
Brand
Cat
Status
Current
Maximum Rating
1400 kVA
Minimum Rating
1000 kVA
Emissions/Fuel Strategy
Low Fuel Consumption
Voltage
380 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Mission Critical, Prime, Continuous
Engine Model
3512 TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
6.69 in / 170 mm
Stroke
7.48 in / 190 mm
Displacement
3161.03 in³ / 51.8 l
Compression Ratio
13.5:1
Aspiration
TA
Fuel System
Direct Unit Injection
Governor Type
Woodward
Length - Maximum
206.6 in / 5249 mm
Width - Maximum
77.8 in / 1975 mm
Height - Maximum
93.2 in / 2367 mm
Dry Weight - Genset (minimum)
22650 lb / 10270 kg
Dry Weight - Genset (maximum)
23170 lb / 10510 kg