Cat® CS Series

Cat® CS – ATS (Spec Grade)

CS - ATS (Spec Grade)

DESCRIPTION

The CS Series – Contactor-type, Open Transition (CS), Delayed Transition (CSD), Closed Transition (CSCT) ATS is equipped with an intuitive full-color touchscreen HMI and is compatible with Ekip Connect software for commissioning and operation.

The CS Series has an array of standard programmable functions and is built for high performance and service with proactive outage mitigation that monitors temperature and contact health.

Product Feature

        
  • Voltage and frequency sensing of both sources and load
  •     
  • USB port to upload/download settings
  •     
  • Available Bluetooth connection and enhanced communication capabilities
  •     
  • Password protection color touchscreen HMI
  •     
  • Integrated help button and menu
  •     
  • Five programmed packages and IO
  •     
  • Contact wear monitoring including real-time status and predicted contact end-of-life (30-1200A only)
  •     
  • Fast controller response to outage recovery and fast switching (<50ms)

Control Panel

        
  •     
  •     
  • TruOne L4 - color touchscreen HMI compatible with Ekip Connect software, with standard programmable functions and IO, and fast controller response to outage recovery and fast switching (<50ms).

Functions

        
  • High current protection and alarm
  •     
  • Wide 200-480V range with auto-configuration of system settings for 30-1200A range
  •     
  • High time-based withstand and closing ratings (WCR)
  •     
  • Short-time withstand ratings in every frame (CS, CSD, and CSCT models)

Standards

        
  •     
  •     
  • UL 1008, NFPA 70, 99, 101 and 110
  •     
  •     
  •     
  • NEMA ICS 10
  •     
  •     
  •     
  • cUL
  •     
  •     
  •     
  • Conducted and radiated emissions - CISPR 11:2009, Class A
  •     
  •     
  •     
  • ESD immunity test - IEC/EN 61000-4-2 Class B
  •     
  •     
  •     
  • Radiated RF, electromagnetic field immunity test - IEC/EN 61000-4-3 10 V/m
  •     
  •     
  •     
  • Electrical fast, transient/burst immunity test - IEC/EN 61000-4-4
  •     
  •     
  •     
  • Surge immunity test - IEC/EN 61000-4-5 0.5 to 2 kV
  •     
  •     
  •     
  • Conducted immunity test - IEC/EN 61000-4-6
  •     
  •     
  •     
  • Voltage dips and interruption immunity - IEC/EN 61000-4-11
  •     
  •     
  •     
  • Harmonic voltage immunity test - IEC/EN 6100-4-13

  • Standard Equipment
  • Optional Equipment
  • Specs
  • Docs

Standard Equipment

  • Control
    • Color touchscreen
    • Voltage and frequency settings: Pick up and Drop out
    • Time Delay Settings: Override momentary, Transfer, Generator stop, Center-OFF (Delayed Transition Type), Pre-transfer, Post-transfer, Elevator Pre-signal, Elevator Post-signal, and Load shead.
    • Source failure detections: No Voltage, Under/Over Voltage, Phase missing, Voltage unbalance, Invalid frequency, and Incorrect phase sequence
  • Additional Features
    • LED indications for ATS, S1 and S2 status
    • Programmable digital inputs/outputs
    • Auto config (voltage, frequency, phase system)
    • Source priority (Source 1/2, No priority)
    • Manual re-transfer
    • In-phase monitor (synchro check)
    • Genset exercising: on-load, off-load
    • In-built power meter module
    • Load shedding
    • Real time clock
    • Event log
    • Predictive maintenance
    • Voltage and current harmonics measuring
  • Accessories
    • Auxiliary contacts for position indication
    • Digital input/output modules (factory programmed)
    • 12-24 VDC aux supply module for controller
    • Communication modules
  • Connectivity Capability
    • Modbus RTU (RS-485)
    • Modbus/TCP
    • Profibus DP
    • ProfiNet Yes
    • DeviceNet
    • Ethernet IP
  • Applications
    • Utility - Utility
    • Utility - Generator
  • UL short circuit withstand ratings
    • Coordinated breaker WCR
    • Time-based WCR
    • Short-time ratings

Optional Equipment

Specs

Overview

Long Name:
Cat® CS – ATS (Spec Grade)
Name:
Cat® CS Series
Brand:
Caterpillar
Status:
Current

Technical Summary

Rating Range
30 - 3000 A
Transfer Type
Open Transition (CS), Delayed Transition (CSD), Closed Transition (CSCT)
Switch Type
Contactor

System Information

Product nodes
UL: 30-200 A, 260-1200 A, 1600-3000 A
Rated Voltage and Frequency
200-480VAC, 50/60 Hz
Phase system
Single and Three
Number of poles
2, 3 and 4
Neutral configuration
Solid neutral, Switched neutral, (Optional) Overlapping neutral
Product type
Open transition (I-II), Delayed Transition (I-O-II), Closed transition (I-O-II) 1600-3000A only

SEE HOW Cat® CS Series COMPARES AGAINST FREQUENTLY COMPARED PRODUCTS.

ATS TruOne - TruControl
Cat® CS Series
CS - ATS (Spec Grade)
Brand
Caterpillar
Status
Current
Rating Range
30 - 3000 A
Transfer Type
Open Transition (CS), Delayed Transition (CSD), Closed Transition (CSCT)
Switch Type
Contactor
Product nodes
UL: 30-200 A, 260-1200 A, 1600-3000 A
Rated Voltage and Frequency
200-480VAC, 50/60 Hz
Phase system
Single and Three
Number of poles
2, 3 and 4
Neutral configuration
Solid neutral, Switched neutral, (Optional) Overlapping neutral
Product type
Open transition (I-II), Delayed Transition (I-O-II), Closed transition (I-O-II) 1600-3000A only
ATS TruOne - TruControl
Cat® CG Series
CG - ATS (General Purpose)
Brand
Caterpillar
Status
Current
Rating Range
30 - 3000 A
Transfer Type
Open Transition (CG), Delayed Transition (CGD)
Switch Type
Contactor
Product nodes
30, 60, 100, 125, 160, 200, 260, 400, 600, 800, 1000, 1200, 1600, 2000, 2600, 3000A
Rated Voltage and Frequency
200-480VAC, 50/60 Hz
Phase system
Single and Three (three phase only >600A)
Number of poles
2, 3 and 4 (3 & 4 pole only >600A)
Neutral configuration
Optional Solid or Switched neutral
Product type
Open transition (I-II), Delayed Transition (I-O-II)
ATS TruOne - TruControl
Cat® CBS Series
CBS - ATS (Spec Grade)
Brand
Caterpillar
Status
Current
Rating Range
100 - 3000 A
Transfer Type
Open Transition (CBS), Delayed Transition (CBSD), Closed Transition (CBSCT), with Bypass Isolation
Switch Type
Contactor
Product nodes
UL: Open transition 100-3000A, Delayed transition 100-3000A, Closed transition 1000-3000A
Rated Voltage and Frequency
200-480VAC, 50/60 Hz
Phase system
Single and Three
Number of poles
2, 3 and 4
Neutral configuration
Solid neutral, Switched neutral, Overlapping neutral (100-1200A only)
Product type
Open transition (I-II), Delayed Transition (I-O-II), Closed transition (I-O-II)