DE350S GC (60 Hz)
DE350S GC Generator Set
C13 (50 HZ) 350-450 kVA Diesel Generator models represent a customizable and flexible solution for your mission critical, standby and prime applications.
DESCRIPTION
The DE350S GC diesel generator sets have been developed for your standby applications. Producing reliable power of 350 ekW at 60 Hz, our C9.3 diesel-powered DE350S GC generator set is designed to ISO 8528-5 transient response requirementsCaterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.Electric PowerCat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
A-Frame Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
GCCP 1.1 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 55°C (131°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
- Standard Equipment
- Optional Equipment
- Specs
- Docs
Standard Equipment
- Engine
- C9.3B, Inline 6 Cylinder, 4 Stroke Diesel
- Air, Cooling & Exhaust
- Standard Air Filter
- Genset Control
- GCCP 1.1
- Governor
- Adem A4
- Alternator
- A Frame Standard Alternator
- Fuel Storage
- Single Wall 8 Hour Tank
- General
- Engine and alternator pre-paint, Caterpillar yellow
Optional Equipment
- Air, Cooling & Exhaust
- 6" Elbow Kit
- No Muffler
- Single Stage Air Filter
- 6" Flange Kit
- 5" Muffler - 10dBA Attenuation
- 5-6" Exhaust Adapter
- Dual Element Air Filter
- 6" Muffler - 25 dBA Attenuation
- 5" Elbow Kit
- Canopy Silencer
- Alternator Requirements
- IP Standard @ 21 FUW A-Frame
- Space Heater
- Auxiliary Supply Voltage
- 240V
- Certification
- Australia, CIS, Gulf Certification
- Certificate of Conformance 13
- Circuit Breaker
- 4 Pole Circuit Breaker 800A
- 4 Pole Circuit Breaker 1250A
- Shunt Trip
- Neutral Earth Link
- 3 Pole Circuit Breaker 630A
- 3 Pole Circuit Breaker 800A
- Circuit Breaker Padlock
- 4 Pole Circuit Breaker 630A
- 3 Pole Circuit Breaker 1250A
- Overload via Alarm Switch on Breaker
- Auxiliary Contacts
- Enclosure
- Cat GC Enclosure
- Fuel Storage
- Low Fuel Level Alarm
- High Fuel Level Alarm
- Fuel Level Sender
- Dual Wall 8 Hour Tank
- Low Fuel Level Shutdown
- Single Wall Tank With Containment 01
- Genset Control
- Coolant Heater
- PLG Cellular 4G E
- Battery Charger
- PLG Ethernet
- Standby Pack (Smart Jacket Water Heater, Battery Charger)
- Oil Temperature Display
- Low Coolant Temperature Alarm
- Voltage Adjust Potentiometer
- Speed Adjust Potentiometer
- PLG Cellular 4G U
- Battery
Specs
Overview
Long Name:
DE350S GC Generator Set
Name:
DE350S GC (60 Hz)
Brand:
Cat
Status:
Current
Generator Set Specifications
Maximum Rating
350 ekW
Minimum Rating
350 ekW
Emissions/Fuel Strategy
Low Fuel, R96/EUIIIa
Voltage
220 to 480 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby
Engine Specifications
Engine Model
C9.3B ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore
4.53 in / 115 mm
Stroke
5.87 in / 149 mm
Displacement
567.5 in³ / 9.3 l
Compression Ratio
16.5:1
Aspiration
Air to Air Aftercooled
Fuel System
Direct Injection
Governor Type
Adem™A4
Generator Set Dimensions
Length - Maximum
186.7 in / 4743 mm
Width - Maximum
79.3 in / 2014 mm
Height - Maximum
84 in / 2133 mm