New | Cat C32 ACERT Generator Set (EPA Tier 3)

C32 ACERT generator sets incorporate a separate circuit aftercooling system (SCAC) for all configurations. The primary advantage of the SCAC systsem is reduced aftercooler corrosion since no sea water circulates through the aftercooler. Many other improvements on these engines contribute to minimizing owning and operating costs. The EPA Tier 3, IMO II, EU Stage IIIA compliant ratings are available with heat exchanger or keel cooled options. Heat exchanger configurations have an optional front mounted sea water pump.

Generator Set Specifications
Minimum Rating730 ekW (913 kVA)
Maximum Rating940 ekW (1175 kVA)
Frequency60hz
Speed1800 rpm
Emissions/Fuel StrategyEPA Tier III
Engine Specifications
AspirationTurbocharged and aftercooled
Bore5.7 in
Stroke6.38 in
Displacement1959 in³
Governor TypeElectronic
Fuel SystemMEUI
Engine ModelVee-12, 4-stroke-Cycle-Diesel
Generator Set Dimensions
Width60.2 in
Height65.6 in
Weight - Estimated15721 lb
Length162.8 in/4271 mm (minimum), 175.3 in/4452 mm (maximum)
Generator Specifications
ExcitationPermanent magnet
Number of Poles4
Number of Bearings2 roller bearings
Number of Leads6
InsulationClass H
IP Rating23
Voltage RegulatorCDVR

U.S. Epa Tier 3 Compliant

Extensive Service Network Of Dealers; Unparalleled Service From Authorized Marine Dealers

Proven Engine Operating History; Performance Iron With Thousands Of Hours Of Validation Testing For Quality And Durability

60 Months Standard Warranty

Heat Exchanger Or Keel Cooling; Heat Exchanger Configurations: Optional Front Mounted Sea Water Pump

Separate Circuit Aftercooling System (scac): No Seawater Circulating Through The Aftercooler

Standard Equipment

AIR INLET SYSTEM
  • Separate circuit after-cooled (SCAC)
  • Turbocharger, jacket water cooled
  • Turbocharger inlet, 152 mm (6 in) OD straight connection
CONTROL SYSTEM
  • If an EMCP panel or MGCP option is not chosen as optional equipment, then start/stop controls must be provided by the customer
  • Electronic diagnostics and fault logging
  • Engine Protection Mode for extended ambient conditions
  • Electronic fuel/air ratio control
COOLING SYSTEM
  • Separate Circuit After-Cooling (SCAC) for Heat Exchanged (HEX) & Keel cooled engines
  • Jacket Water (JW) and SCAC Heat Exchangers Shell & Tube for HEX cooled engines
  • SCAC pump, gear driven
  • Jacket water pump, gear driven
  • Sea water pump, bronze impeller, gear driven, for HEX cooled engines only
  • Jacket water HEX with Sea water pump Connections: 76.2 mm (3in) ID Standard
  • 4 Bolt ANSI Flange Connection
  • Jacket water HEX without Sea water pump Connection: 2.5" hose barb connection (inlet), 76.2 mm (3in) ID Standard 4 Bolt ANSI Flange (outlet)
  • Keel Connections: 76.2 mm (3in) ID Standard 4 Bolt ANSI Flange Connection
  • SCAC and JW shunt tanks for maintaining proper Pump inlet pressures
EXHAUST SYSTEM
  • Water-cooled exhaust manifold & turbocharger
  • 4 Bolt 130 mm (5.12 in) diameter flanged outlet
FLYWHEELS & FLYWHEEL HOUSINGS
  • Flywheel Housing, SAE No. 0
  • Flywheel, 18 inch, 136 teeth
  • SAE standard rotation
FUEL SYSTEM
  • Duplex Fuel Filters, Spin-on, RH service
  • Fuel connections size: Supply JIC 37 Deg -10 (7/8-14), Return JIC 37 Deg -8 (3/4-16)
  • Plate-type fuel cooler installed behind Aftercooler Shunt Tank
  • Fuel transfer pump, gear driven
  • Manual fuel priming pump
GENERATORS AND GENERATOR ATTACHMENTS
  • SR5 form wound
  • 2 roller bearings
  • Permanent magnet excitation
  • 4 pole, 6 leads, Series Star connected
  • Caterpillar's Digital Voltage Regulator (CDVR)
  • Marine Class H insulation, Class F temperature rise
  • Surface mounted platinum (PT100) 3-wire RTDs, 2 per phase on stator and one each on support bearings
  • Anti-condensation space heaters (2 elements - 240 VAC, 1000 Watts
  • IP23 Protection suitable for use with Fixed Water Based Local Application Fire Fighting Systems (FWBLAFFS)
  • System IV insulation for harsh environment protection
LUBE SYSTEM
  • Simplex oil filters, RH service
  • Deep sump oil pan
  • RH service oil filler locations
  • RH service dipstick
  • Oil pump, gear driven
MOUNTING SYSTEM
  • Formed C-channel rails, 300mm (11.81in) height
  • Six shipped loose combined helical spring/rubber
  • isolators for installation below package base
GENERAL
  • Front Damper guard
  • Common electrical bondng point on HEX and KEEL cooled engines

Optional Equipment

ALARM AND PROTECTION
  • Remote panels
  • MCS Controller
  • Power analyzer module
  • Oil level, exhaust temperature, air starting pressure, heat exchanger pressure sensors
EXHAUST SYSTEM
  • Dry Elbows
  • Flexible Fitting
  • Flange
  • Muffler
  • Muffler Spark Arresting
  • Rain Cap
AIR INLET SYSTEM
  • Air Inlet Cleaner
  • Closed Crankcase Ventilation
  • Air inlet adapter
CHARGING SYSTEM
  • Battery Chargers, Charging Alternators
CONTROL SYSTEM
  • Load Sharing Attachment
FUEL SYSTEM
  • Water Separator
LUBE SYSTEM
  • Duplex Oil Filters, Sump Pump
PROTECTION SYSTEM
  • Fuel and Oil Shielding
STARTING SYSTEM
  • Electric Starting Motors - Single 24 Volt
  • Air Starting Motor
  • Dual Starting Motors (Electric and Air)
  • Air Start Accessories
  • Starting Aids - JW Heaters
  • Battery Sets - 24 Volt - Dry

listofrelationships

original

Other Models in this Category

Select Marine Power System Type


Hawthorne Power Systems Logo

Request a Quote

Why Cat is Better. Machine Comparison

"
With only a few days notice, we were able to get the emergency system working properly. Hawthorne Cat provided great leadership and excellent field support.
Mark Cripe
Helix Electric
"

San Diego - Power
Kyle Farmer
Engine Business Manager
858.376.6821 office
760.715.9565 mobile
kfarmer@hawthornecat.com

Tim Roberts
Product Support
General Manager
858.376.6820 office
858.583.8460 mobile
troberts@hawthornecat.com

Mark Reza
Used Engine Sales Manager
858.376.6840 office
858.688.0076 mobile
mreza@hawthornecat.com

Phillip J. Smith (PJ)
Field Service Manager
858.376.6874 office
858.688.0134 mobile
psmith@hawthornecat.com

Hawaii – Power
Cliff Yuen
Director of Sales & Rentals
808.676.0322 office
808.349.7767 mobile
cyuen@hawthornecat.com

Guam – Power
Myver Hecita
Power Systems Rental &
Sales Representative
671.649.4241 office
671.898.2740 mobile
mhecita@hawthornecat.com